Method for analyzing weak link in fire of nuclear power plant
A treatment method and weak link technology, applied in the field of fire weak link analysis, can solve problems such as high price, high construction requirements, increase power plant operation and maintenance costs, and achieve the effect of reducing quantity and saving engineering cost
- Summary
- Abstract
- Description
- Claims
- Application Information
AI Technical Summary
Problems solved by technology
Method used
Image
Examples
Embodiment 1
[0053] ①In the nuclear fuel plant (KX plant), determine a column A safety fire protection space 3ZFSK0081A to be analyzed.
[0054] ②According to criteria a) and b), the following potential common mode points are found:
[0055] The limit switches of the two redundant column valves EAS013VB (Column A) and EAS014VB (Column B) are located in this safe fire protection space. According to the criteria of c) and d), there is no potential common mode point in this safe fire protection space.
[0056] ③Functional analysis:
[0057] These two valves are the isolation valves of the pit suction line of the containment spray pump (EAS001PO / 002PO). EAS013VB / 014VB is closed under normal operating conditions of the unit. In order to ensure the containment spray function, the valve is opened during the cyclic spray phase of the containment spray system. When receiving the "EAS013VB (EAS014VB) open" signal, at the same time as "EAS013VB (EAS014VB) is fully open", the containment spray pump refuelin...
Embodiment 2
[0064] ①In the nuclear fuel plant (KX plant), determine a 3ZFSK0280A column A to be analyzed.
[0065] ②According to criteria a) and b), the following potential common mode points are found:
[0066] That is to say, it was found that most of the A and B columns of the atmospheric monitoring subsystem (DVK) in the containment are located in the safe fire protection space. According to the criteria of c) and d), there is no potential common mode point in this safe fire protection space.
[0067] ③Functional analysis:
[0068] In the DVK system, only the small flow exhaust sub-system is a safety-related system. This system is used to reduce radioactive pollution in the bottom air after LOCA or nuclear fuel loading and unloading accidents. Therefore, from the perspective of functional analysis, the common mode point is confirmed.
[0069] ④ Fire risk analysis
[0070] This safe and fireproof space is not PFG. The room where the relevant equipment of the small flow exhaust sub-system is l...
PUM
Abstract
Description
Claims
Application Information
- R&D Engineer
- R&D Manager
- IP Professional
- Industry Leading Data Capabilities
- Powerful AI technology
- Patent DNA Extraction
Browse by: Latest US Patents, China's latest patents, Technical Efficacy Thesaurus, Application Domain, Technology Topic, Popular Technical Reports.
© 2024 PatSnap. All rights reserved.Legal|Privacy policy|Modern Slavery Act Transparency Statement|Sitemap|About US| Contact US: help@patsnap.com